Exams › GATE › Technical
The positive, negative and zero-sequence impedances of a three-phase generator are \(Z_1\), \(Z_2\), and \(Z_0\), respectively. For a line-to-line fault with fault impedance \(Z_f\), the fault current is \(I_{f1} = k I_f\), where \(I_f\) is the fault current with zero fault impedance. The relation between \(Z_f\) and \(k\) is
- \(Z_f = (Z_1 + Z_2)(1-k)/k\)
- \(Z_f = (Z_1 + Z_2)(1+k)/k\)
- \(Z_f = (Z_1 + Z_2)k/(1-k)\)
- \(Z_f = (Z_1 + Z_2)k/(1+k)\)
Correct answer: \(Z_f = (Z_1 + Z_2)(1-k)/k\)
Solution
In a line-to-line fault, the positive and negative sequence networks are in series, so the fault current depends on \(Z_1 + Z_2 + Z_f\). If the current with fault impedance is \(k\) times the zero-impedance fault current, equating the two expressions gives the required relation. Solving yields \(Z_f = (Z_1 + Z_2)(1-k)/k\).
Related GATE Technical questions
- Consider the two power systems shown in Figure A, which are initially not interconnected and are operating in steady state at the same frequency. Separate load-flow solutions are computed individually for the two systems, and the bus voltage phasors obtained are indicated in Figure A. These two isolated systems are now interconnected by a short transmission line as shown in Figure B, and it is found that \(P_1=P_2=Q_1=Q_2=0\). The bus voltage phase angular difference between generator bus X and generator bus Y after the interconnection is:
- A three-bus network is shown in the figure below, indicating the p.u. impedances of each element. The corresponding bus admittance matrix is
- Statement for Linked Answer Questions 52 and 53: Two generator units $G_1$ and $G_2$ are connected by a 15 kV line with a bus at the midpoint, as shown below. $G_1 = 250$ MVA, 15 kV, positive-sequence reactance $X = 25\%$ on its own base $G_2 = 100$ MVA, 15 kV, positive-sequence reactance $X = 10\%$ on its own base $L_1$ and $L_2 = 10$ km, positive-sequence reactance $X = 0.225\ \Omega$/km For the above system, the positive-sequence diagram with the p.u. values on the 100 MVA common base is
- In the above system, the three-phase fault MVA at bus 3 is
- For a fully transposed transmission line,
- A power system has 100 buses, including 10 generator buses. For load-flow analysis using the Newton–Raphson method in polar coordinates, the size of the Jacobian is
⚔️ Practice GATE Technical free + battle 1v1 →