Statement for Linked Answer Questions 52 and 53: Two generator units $G_1$ and $G_2$ are connected by a 15 kV line with a bus at the midpoint, as shown below. $G_1 = 250$ MVA, 15 kV, positive-sequence reactance $X = 25\%$ on its own base $G_2 = 100$ MVA, 15 kV, positive-sequence reactance $X = 10\%$ on its own base $L_1$ and $L_2 = 10$ km, positive-sequence reactance $X = 0.225\ \Omega$/km For the above system, the positive-sequence diagram with the p.u. values on the 100 MVA common base is
- (A)
- (B)
- (C)
- (D)
Correct answer: (A)
Solution
To draw the positive-sequence diagram on a 100 MVA base, each generator reactance is converted from its own base to the common base, and the line reactances are converted from ohms to per unit using the 15 kV base. The resulting per-unit values match diagram (A).
Related GATE Technical questions
- Consider the two power systems shown in Figure A, which are initially not interconnected and are operating in steady state at the same frequency. Separate load-flow solutions are computed individually for the two systems, and the bus voltage phasors obtained are indicated in Figure A. These two isolated systems are now interconnected by a short transmission line as shown in Figure B, and it is found that \(P_1=P_2=Q_1=Q_2=0\). The bus voltage phase angular difference between generator bus X and generator bus Y after the interconnection is:
- A three-bus network is shown in the figure below, indicating the p.u. impedances of each element. The corresponding bus admittance matrix is
- In the above system, the three-phase fault MVA at bus 3 is
- For a fully transposed transmission line,
- A power system has 100 buses, including 10 generator buses. For load-flow analysis using the Newton–Raphson method in polar coordinates, the size of the Jacobian is
- The inductance and capacitance of a 400 kV, three-phase, 50 Hz lossless transmission line are 1.6 mH/km/phase and 10 nF/km/phase, respectively. The sending-end voltage is maintained at 400 kV. To maintain a voltage of 400 kV at the receiving end while the line delivers a 300 MW load, the shunt compensation required is
⚔️ Practice GATE Technical free + battle 1v1 →