Exams › GATE › Technical
For a fully transposed transmission line,
- positive, negative and zero sequence impedances are equal
- positive and negative sequence impedances are equal
- zero and positive sequence impedances are equal
- negative and zero sequence impedances are equal
Correct answer: positive and negative sequence impedances are equal
Solution
In a fully transposed transmission line, the phase impedances are averaged over the line length, making the positive- and negative-sequence impedances equal. The zero-sequence impedance is generally different because the return path is not the same. Hence, positive and negative sequence impedances are equal.
Related GATE Technical questions
- Consider the two power systems shown in Figure A, which are initially not interconnected and are operating in steady state at the same frequency. Separate load-flow solutions are computed individually for the two systems, and the bus voltage phasors obtained are indicated in Figure A. These two isolated systems are now interconnected by a short transmission line as shown in Figure B, and it is found that \(P_1=P_2=Q_1=Q_2=0\). The bus voltage phase angular difference between generator bus X and generator bus Y after the interconnection is:
- A three-bus network is shown in the figure below, indicating the p.u. impedances of each element. The corresponding bus admittance matrix is
- Statement for Linked Answer Questions 52 and 53: Two generator units $G_1$ and $G_2$ are connected by a 15 kV line with a bus at the midpoint, as shown below. $G_1 = 250$ MVA, 15 kV, positive-sequence reactance $X = 25\%$ on its own base $G_2 = 100$ MVA, 15 kV, positive-sequence reactance $X = 10\%$ on its own base $L_1$ and $L_2 = 10$ km, positive-sequence reactance $X = 0.225\ \Omega$/km For the above system, the positive-sequence diagram with the p.u. values on the 100 MVA common base is
- In the above system, the three-phase fault MVA at bus 3 is
- A power system has 100 buses, including 10 generator buses. For load-flow analysis using the Newton–Raphson method in polar coordinates, the size of the Jacobian is
- The inductance and capacitance of a 400 kV, three-phase, 50 Hz lossless transmission line are 1.6 mH/km/phase and 10 nF/km/phase, respectively. The sending-end voltage is maintained at 400 kV. To maintain a voltage of 400 kV at the receiving end while the line delivers a 300 MW load, the shunt compensation required is
⚔️ Practice GATE Technical free + battle 1v1 →