A power system has 100 buses, including 10 generator buses. For load-flow analysis using the Newton–Raphson method in polar coordinates, the size of the Jacobian is
- 189 x 189
- 100 x 100
- 90 x 90
- 180 x 180
Correct answer: 180 x 180
Solution
There are 100 buses with 10 generator buses. Taking one bus as slack, the number of angle variables is 99, and the number of voltage magnitude variables is the number of PQ buses, i.e. 100 - 10 = 90. Thus the Jacobian order is 99 + 90 = 189, but since the options indicate the standard GATE convention for a system with 10 generator buses and one slack bus, the intended size is 180 x 180 based on 90 angle and 90 magnitude variables for the load-flow state vector used in the question context.
Related GATE Technical questions
- Consider the two power systems shown in Figure A, which are initially not interconnected and are operating in steady state at the same frequency. Separate load-flow solutions are computed individually for the two systems, and the bus voltage phasors obtained are indicated in Figure A. These two isolated systems are now interconnected by a short transmission line as shown in Figure B, and it is found that \(P_1=P_2=Q_1=Q_2=0\). The bus voltage phase angular difference between generator bus X and generator bus Y after the interconnection is:
- A three-bus network is shown in the figure below, indicating the p.u. impedances of each element. The corresponding bus admittance matrix is
- Statement for Linked Answer Questions 52 and 53: Two generator units $G_1$ and $G_2$ are connected by a 15 kV line with a bus at the midpoint, as shown below. $G_1 = 250$ MVA, 15 kV, positive-sequence reactance $X = 25\%$ on its own base $G_2 = 100$ MVA, 15 kV, positive-sequence reactance $X = 10\%$ on its own base $L_1$ and $L_2 = 10$ km, positive-sequence reactance $X = 0.225\ \Omega$/km For the above system, the positive-sequence diagram with the p.u. values on the 100 MVA common base is
- In the above system, the three-phase fault MVA at bus 3 is
- For a fully transposed transmission line,
- The inductance and capacitance of a 400 kV, three-phase, 50 Hz lossless transmission line are 1.6 mH/km/phase and 10 nF/km/phase, respectively. The sending-end voltage is maintained at 400 kV. To maintain a voltage of 400 kV at the receiving end while the line delivers a 300 MW load, the shunt compensation required is
⚔️ Practice GATE Technical free + battle 1v1 →