A single-phase 50 kVA, 250 V/500 V two-winding transformer has an efficiency of 95% at full load, unity power factor. If it is reconfigured as a 500 V/750 V autotransformer, its efficiency at its new rated load at unity power factor will be

  1. 95.752%
  2. 97.851%
  3. 98.276%
  4. 99.241%

Correct answer: 98.276%

Solution

From 95% efficiency at 50 kVA and unity power factor, the transformer losses can be found. When reconfigured as a 500 V/750 V autotransformer, the power rating increases, while the losses remain approximately the same, leading to a higher efficiency of 98.276%.