A 3-phase, 11 kV, 10 MVA synchronous generator is connected to an inductive load of power factor (√3/2) via a lossless line with a per-phase inductive reactance of 5 Ω. The per-phase synchronous reactance of the generator is 30 Ω with negligible armature resistance. If the generator is producing the rated current at the rated voltage, then the power factor at the terminal of the generator is
- 0.63 lagging.
- 0.87 lagging.
- 0.63 leading.
- 0.87 leading.
Correct answer: 0.87 lagging.
Solution
The correct option is right because the power factor at the terminal of the generator is determined by the relationship between the voltage, current, and the reactances involved. Given the inductive load and the reactance values, the resulting power factor is calculated to be 0.87 lagging, indicating that the load is drawing reactive power, which is typical for inductive loads.
Related GATE Technical questions
- If the input x(t) and output y(t) of a system are related as y(t) = max(0, x(t)), then the system is
- Two discrete-time linear time-invariant systems have impulse responses h1[n] = δ[n−1] + δ[n+1] and h2[n] = δ[n−1] + δ[n+1], where δ[n] is the Kronecker delta. The overall system is
- Consider a power system consisting of N number of buses. Buses in this power system are categorized into slack bus, PV buses and PQ buses for load flow study. The number of PQ buses is N_L. The balanced Newton-Raphson method is used to carry out load flow study in polar form. H, S, M, and R are sub-matrices of the Jacobian matrix J as shown below:
[ΔP]
[ΔQ] = J [Δδ]
[ΔV], where J = [H S
M R]
The dimension of the sub-matrix M is
- Inductance is measured by
- In the Nyquist plot of the open-loop transfer function G(s)H(s) = (3s + 5)/(s - 1) corresponding to the feedback loop shown in the figure, the infinite semi-circular arc of the Nyquist contour in s-plane is mapped into a point at
- Consider a unity-gain negative feedback system consisting of the plant G(s) (given below) and a proportional-integral controller. Let the proportional gain and integral gain be 3 and 1, respectively. For a unit step reference input, the final values of the controller output and the plant output, respectively, are
G(s) = 1/(s - 1)
⚔️ Practice GATE Technical free + battle 1v1 →